Overview

The PVFY Vertical Ducted unit is ideal for installations in closets or equipment rooms where space is limited. It features a side drain pan allowing it to be installed in a horizontal left position. PVFY vertical air handlers can be connected to a system with all other CITY MULTI indoor units for complete system design flexibility.

  • Capacities between 12,000-54,000 Btu/h
  • Extremely quiet, with sound ratings as low as 29 dB(A)
  • An adjustable blower static pressure of 0.30" or 0.50" W.G.
  • High efficiency DC Motors and a forward curved blower provide quiet efficient operation
  • The control board allows an easy connection for a condensate overflow safety switch
  • The cabinets are constructed of heavy gauge pre-painted steel with one-inch insulation providing an R-4.2 insulating value
  • Down flow kit available
Model Specifications
Power Source Voltage, Phase, Cycle 208 / 230V, 1-phase, 60Hz
Cooling Capacity (Nominal) 12000 Btu/h (3.52 kW) *1
Capacity Cooling 12000 Btu/h (3.5 kW) *1
Heating 13500 Btu/h (4 kW) *1
Heating Capacity (Nominal) 13500 Btu/h (3.96 kW) *1
Power Consumption Cooling 0.07 / 0.07 kW
Heating 0.07 / 0.07 kW
Minimum Circuit Ampacity (MCA) (208/230V) 0.56 / 0.50 Ampere
Minimum Circuit Ampacity MCA 0.86/0.76 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Recommended Fuse/Breaker Size 0.86/0.76 Ampere
Refrigerant Type R410A
Fan Motor type High-efficiency DC
Airflow Rate - 0.30 ESP (0.50 ESP) 243-320-376 CFM (202-249-346 CFM) *2
External Static Pressure 0.30 / 0.50 (Selectable) In. W.G. (75 / 125 Pa)
Air Filter Filter and rack - field-supplied
Dimensions H x W x D Height 42-3/4 Inches (1086 mm)
Width 17-3/4 Inches (451 mm)
Depth 21 Inches (533 mm)
Net Weight 88 Lbs. (40 kg)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 1/2 Inch (12.7 mm) Flare
Liquid (High Pressure) 1/4 Inch (6.35mm) Flare
Operating Temperature Range Cooling (Outdoor) 95°F (35°C) DB
Heating (Outdoor) 47°F (8°C) DB / 43°F (6°C) WB