Heat Recovery Systems

CITY MULTI VRF - Air Source

R2-Series H2i™

Overview
The Hyper-Heating INVERTER (H2i™) R2-Series simultaneously cools and heats different zones within a building to provide energy saving heat recovery operation.

Our 2-pipe H2i R2-Series gives you the flexibility to fit the specific needs of any building and provides reliable cold-climate heating performance.
  • Innovative flash injection technology for tremendous heating capacity at lower outdoor temperatures
  • Built-in base pan heater to prevent ice in drain pan (T models)
  • 2-pipe, air-source, simultaneous cooling and heating
  • INVERTER-driven compressor
  • Connects to CITY MULTI® indoor units
  • Connectable capacity of 50% to 150%
  • Controlled via CITY MULTI® Controls Network
  • Provides up to 100% heating capacity at 0° F outdoor ambient
  • Provides up to 85% heating capacity at -13° F outdoor ambient
Model Specifications
Power Source Voltage, Phase, Cycle 208 / 230V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 144000 Btu/h (42.2 kW) 1
Power Input (Nominal) 10.85 kW 3
Heating Capacity (Nominal) 160000 Btu/h (46.9 kW) 1
Power Input (Nominal) 13.16 kW 3
Minimum Circuit Ampacity MCA 44 / 40 Ampere
Maximum fuse size (time delay) 60 Ampere
Recommended Fuse/Breaker Size 50 Ampere
Refrigerant Type R410A
Charge R410A x 26 lbs + 1 oz (11.8 kg)
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Fan Airflow Rate 6200 CFM (175 m³/min) / 6200 CFM (175 m³/min)
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150 % of outdoor unit capacity
Model (Quantity) P06~P96 / 1~36
Refrigerant Pipe Size O.D. Liquid (High Pressure) 7/8 Inch (22.2 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23 ~ 115° F (-5 ~ +46° C) **
Heating (Outdoor) -13~60° F(-25~15.5° C)